Inspection Status: Approved
Inspection History: FIREWALL/FIREBARRIER/FIRESTOP
| Date |
Description |
Inspector |
Results |
Comments |
| 06/16/2014 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Approved |
IVRS - Inspection :* |
| 05/05/2014 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
IVRS - Inspection :* |
| 05/05/2014 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
STAIRWELL FIRESTOP SYSTEM OK TO COVER. CHECKED VENTING AT CLOSET TANKS, WESTSIDE, 2ND FLOOR. OK TO COVER DWV, 2ND FLOOR A TO D & 1 TO 7. ALSO, OK TO COVER PEX IN SAME AREAS. OK TO SHEETROCK 2ND FLOOR A TO D & 1 TO 7. |
| 04/30/2014 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
IVRS - Inspection :* |
| 04/30/2014 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
A-D, 1-4 2ND LEVEL OK TO ONE SIDE. PROVIDE MIN 1 1/4" CLEARANCE AT MC CABLES. EACH DRY VENT SHALL RISE VERTICALLY BEFORE OFFSET. CARRIERS AS REQ SADDLES SPECIFIED ON DUCT |
| 04/11/2014 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
IVRS - Inspection :* |
| 04/11/2014 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
FINISH ALL FIRE STOP SYSTEMS 1ST FLOOR. OK TO TAPE 1ST FLOOR. PROVIDE BUSHINGS @ FAN COILS FOR REFER LINES. |
| 03/24/2014 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
IVRS - Inspection :* |