Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/08/2013 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 11/07/2013 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 10/28/2013 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 10/28/2013 |
MECHANICAL - FINAL |
|
Partial Approval |
COAT EXPOSED ARMFLEX. EXHAUST FAN MUST BE SEALED TO TOP OF DUCT. CONDENSORS ARE OVERFUSED. FINISH CONNECTING HOT DOG CART. PROVIDE AIR BALANCE REPORT. PROVIDE CAPTURE & CONTAINMENT TEST & HEAT SENSOR TEST. FINISH CONDENSATE DRAIN. PROVIDE STERILIZATION REPORT & ANY BACKFLOW CERTS. PROVIDE MIXING VALVES AS PER PLAN. INSTALL BACKFLOW DEVICE. |