Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T13CM04588

Parcel: 14018002C

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Permit Number - T13CM04588

Inspection Description - MECHANICAL - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
08/06/2013 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
08/06/2013 MECHANICAL - FINAL Not ready for Inspection 1. PROVIDE LADDER FOR ROOF ACCESS
2. DO NOT CALL FOR INSPECTIONS UNTIL READY OR RE-FEE WILL BE ATTACHED
08/02/2013 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
08/02/2013 MECHANICAL - FINAL Not ready for Inspection 1. DEAD FRONT MISSING FROM DISCONNECT BOX
2. WHITE WIRE NOT TO BE USED AS HOT LEG
3. INCORRECT FUSES, OVERFUSED
4. LINE SET INSULATION NOT PROPERLY COATED FOR UV PROTECTION, USE NO TAPE
5. ROOF JACK NOT PROPERLY SEALED