Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2013 | FIRE SPKLR - FINAL | Approved | ||
| 09/09/2013 | FIRE SPKLR - FINAL | Denied | 1. Two painted sprinkler heads above the drop ceciling need to replace 2. Correct upright sprinkler coverage above front door blocked by 2x4 wood 3. Need the following inspection reports: Annual sprinkler Annual fire alarm 5 year check valve inspection |
|
| 08/29/2013 | FIRE SPKLR - FINAL | Denied | 1. Remove tape from sprinkler heads. 2. Needs to be at least 1 inch space between deflector and insulation. |