Permit: T13CM04488

Parcel: 133071360

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/18/2013 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
09/16/2013 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/16/2013 PLUMBING - ROUGH, SOIL Denied VENT IS REQUIRED TO RISE VERTICALLY W/OUT HORIZONTAL OFFSET. BLAKE TEE IS NOT APPROVED FOR HORIZONTAL USE. PROVIDE A WYE PATTERN DRAINAGE FITTING FOR TEST. INSTALL A CLEANOUT IN WALL ON VENT. FOAM WRAP REQUIRED AT CONCRETE PENETRATION.