Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T13CM04487
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
08/05/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/05/2013 | BUILDING - FINAL | Denied | 1. OSA TOO CLOSE TO WASTE VENT 2. DUCT JOINTS NOT SEALED 3. UNIT DATA PLATES NOT IDENTIFIED 4. UNITS OVER-FUSED 5. ELECTRICAL TO UNITS NOT PROPERLY INSTALLED 6. CONDENSATE NOT COATED 7. CONDENSATE NOT PROPERLY SUPPORTED 8. CONDENSATE NOT PROPERLY TERMINATED 9. GAS PIPE NOT PROPERLY SUPPORTED 10. NO DRIP LEGS PROVIDED 11. DO NOT RE-USE FLEX CONNECTORS PER UPC 12. DUCT NOT PROPERLY SUPPORTED, FLEX CONNECTOR NOT TO SUPPORT DUCT 13. FLUE EXHAUST WITHIN 10' OF O.S.A. INTAKE 14. PROVIDE APPROVED LABELING OF ROOF TOP EQUIPMENT SHARPIE NOT AN APPROVED METHOD 15. BALANCE REPAORT INCOMPLETE 16. ANY FURTHER FAILED INSPECTIONS WILL RESULT IN A RE-FEE |
|
07/30/2013 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |