Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2013 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/28/2013 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/28/2013 | ELECTRIC - INTERMEDIATE | Denied | 1. SUB-PANEL MISSING PLASTIC BUSHING & #10 SCREWS & GROUND BAR 2. BACK PORCH J BOX GROUNDING MAKEUP NOT TO CODE 245. OUTLET TO BE GFI 3. SUNROOM PANCAKE BOX NOT INSTALLED TO CODE 245. BANG PLATES MISSING. ROMEX TO BE 1 1/4 FROM EDGE OF STUD 4. WHERE ARE PLANS? |