Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2013 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 08/23/2013 | ELECTRIC - UNDERGROUND | Partial Approval | FROM WEST OF STREET TO SIGN PVC IN TRENCH OK | |
| 08/13/2013 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 08/13/2013 | ELECTRIC - UNDERGROUND | Partial Approval | ENCASEMENT FROM TRANSFORMER TO SERVICE PANEL OK | |
| 08/08/2013 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 08/08/2013 | ELECTRIC - UNDERGROUND | Partial Approval | ENCASE IN CONCRETE 300.5 AT 18", 4" THICK OK | |
| 08/06/2013 | ELECTRIC - UNDERGROUND | Partial Approval | GROUND RODS & PEDESTAL 2 1/2 PVC FOR EAST & WEST SIGNS OK | |
| 08/05/2013 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 08/05/2013 | ELECTRIC - UNDERGROUND | Partial Approval | 1. ACROSS ROADWAY EASTSIDE 2.1" PVC OK TO SIGN WITH 2 POTHOLES 2. WEST ROADWAY WITH 2 POTHOLES OK |