Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/30/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/30/2013 | ELECTRIC - FINAL | Denied | 1. PANEL NOT GROUNDED 2. SECURE PANEL TO BUILDING PER CODE 3. SECURE CONDUIT TO CODE 4. SEAL KNOCKOUTS BOTTOM DISCONNECT 5. REPAIR SUBPANEL CONNECTOR TO METER BOX 6. REPLACE SHARP POINT SCREW INTO SUBPANEL DEAD FRONT 7. LABEL CIRCUITS 8. MIXED BREAKER TYPE 9. OMIT ALL ELECTRICAL REAR STORAGE NOT TO CODE OR PERMIT 10. ALL ADDITIONS SHOULD BE ON RECORD |
|
| 07/22/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/22/2013 | ELECTRIC - FINAL | Denied | INCOMPLETE INSPECTION. SOME ELEC NOT TO CODE |