Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2013 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/31/2013 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/31/2013 | PLUMBING - INTERMEDIATE | Partial Approval | OK EXCEPT FOR REMAINING PLAN SPECS | |
| 10/29/2013 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/29/2013 | PLUMBING - INTERMEDIATE | Denied | DWC TEST THRU ROOF OK. SUPPORT ABS IN WALLS. PROVIDE DOCUMENTATION FOR ALL CHANGES TO PLAN SPECS. ABS SPECIFIED. L COPPER SPECIFIED. DOMESTIC WATER IS NOT SIZED PER PLAN, CORRECT OR REVISE. PEX REQUIRES 18" FROM SWEAT JOINTS, PROPER SUPPORTS AND ISOLATION. SEE NOTE 7. PIPE INSULATION SPECIFIED. REMOVE EXCESS FLUX FROM COPPER JOINTS. INSTALL BACKING AT MS, FHA STRAPS. SECURE DROP EAR ELS. | |
| 10/25/2013 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/25/2013 | PLUMBING - INTERMEDIATE | Not ready for Inspection | NO TEST ON DWV |