Permit: T13CM04150

Parcel: 11007414D

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T13CM04150

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2013 BUILDING - FINAL Approved IVRS - Inspection :*
11/25/2013 BUILDING - FINAL Approved OK FOR C OF O
11/21/2013 BUILDING - FINAL Partial Approval IVRS - Inspection :*
11/21/2013 BUILDING - FINAL Partial Approval STEP UP CONDENSATE TO 1" AT 1ST TEE ON ROOF. RELOCATE DISCONNECT FROM INSIDE A/C UNIT. PROVIDE A BUSHING IN DISCONNECT FOR A/C NORTH UNIT. PROVIDE A PROTECTIVE COATING ON EXPOSED ARM FLEX. PROVIDE THE GREASE RECEPTOR FOR EXHAUST FAN. LEVEL THE CONDENSING UNIT ON ROOF. AIR BALANCE REPORT & STERILIZATION REPORTS OK. CAPTURE & CONTAINMENT TEST OK.