Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T13CM04150
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/25/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
11/25/2013 | BUILDING - FINAL | Approved | OK FOR C OF O | |
11/21/2013 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
11/21/2013 | BUILDING - FINAL | Partial Approval | STEP UP CONDENSATE TO 1" AT 1ST TEE ON ROOF. RELOCATE DISCONNECT FROM INSIDE A/C UNIT. PROVIDE A BUSHING IN DISCONNECT FOR A/C NORTH UNIT. PROVIDE A PROTECTIVE COATING ON EXPOSED ARM FLEX. PROVIDE THE GREASE RECEPTOR FOR EXHAUST FAN. LEVEL THE CONDENSING UNIT ON ROOF. AIR BALANCE REPORT & STERILIZATION REPORTS OK. CAPTURE & CONTAINMENT TEST OK. |