Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/01/2013 | MECHANICAL - FINAL | Denied | P TAPE IS NOT AN APPROVED SUPPORT - ALSO, COPPER MAY NOT TOUCH METAL. CORRECT SLOPE OF CONDENSATE. SUPPORT & SECURE DRAIN PIPE. |
|
| 07/26/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/26/2013 | MECHANICAL - FINAL | Denied | SUPPORT CONDENSATE PIPING. ALSO, PROVIDE PROPER ALIGNMENT OF FITTINGS AND PVC PRIMER ON ALL SOLVENT CEMENT JOINTS. SUPPORT LINES SET, CORRECT GAPS IN DAMAGE TO INSULATION. VENT TOUCHING WOOD AT ROOF. INSTALL CARBON MONOXIDE DETECTOR. |