Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2013 | FIRE - FINAL | Approved | ||
| 09/19/2013 | FIRE - FINAL | Denied | Need ansul system on the fire alarm monitoring system | |
| 09/11/2013 | FIRE - FINAL | Denied | 1. Need to have the ansul fire extinguisher system that is installed for the hood monitored on the fire alarm system 2. Will need annual fire alarm inspection completed. 3. Need to post exit signage for patio exits also need to be battery back type. 4. Post occupant load sign by front door for inside dinning 140 and patio by patio door 82 5. Need fire extinguishers one for every 1500 sq ft of building 2A-10BC type. 6. Correct sprinkler coverage for overhangs on both east and west sides of the building anything over 4 feet wide shall be sprinkler, if area is combustible construction than upright coverage is also needed. 7. Change out all sprinkler heads that have grease build up in the kitchen area. 8. Replace calculations plate on riser not able to read the one that is there now, new plate shall have etched info on it not ink written. 9.Will need an annual sprinkler inspection and 5 year check valve inspection completed. 10. Replace all signage on riser all are not legible. |