Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2013 | FIRE SPKLR - FINAL | Approved | ||
| 09/11/2013 | FIRE SPKLR - FINAL | Denied | 1. Correct sprinkler coverage for overhangs on both east and west sides of the building anything over 4 feet wide shall be sprinkler, if area is combustible construction than upright coverage is also needed. Will need an approved plan and permit for this work. 2. Change out all sprinkler heads that have grease build up in the kitchen area. 3. Replace calculations plate on riser not able to read the one that is there now, new plate shall have etched info on it not ink written. 4. Will need an annual sprinkler inspection and 5 year check valve inspection completed. 5. Replace all signage on riser all are not legible. |