Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2013 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* | |
| 07/23/2013 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 07/19/2013 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/08/2013 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/08/2013 | ELECTRIC - RECONNECT | Denied | 1. ELECTRIC SERVICE HAS BEEN UPGRADED RECENTLY, NO TEP SEAL AT METER OR TEP CONNECTIONS POA. REVISE PERMIT TO REFLECT SERVICE UPGRADE OR INCREASE TO 100 AMP 2. WIRING AT SECURITY LT IN CARPORT NOT TO CODE 3. PLUG UNUSED OPENING, CONDUIT AT DISC SW EAST OUTSIDE OF HOUSE 4. CEILING FAN WIRED WITH ZIP CORD (SWAG CHAIN) NOT TO CODE USE QUALIFIED ELECTRICIAN TO DO WORK |