Permit: T13CM04033

Parcel: 13602002L


Addresses:

8240 E 22ND ST #111


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T13CM04033

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2013 PLUMBING - FINAL Approved IVRS - Inspection :*
09/23/2013 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
09/23/2013 PLUMBING - FINAL Not ready for Inspection BEV EQUIPMENT W/ BACKFLOW PROTECTION REQUIRED FOR FINAL. ICE MAKER, OVENS OK. COMPLETE ALL WORK, PROVIDE ALL DOCUMENTATION REQUIRED. SEAL FIXTURES AT WALL CONTACT. PROVIDE APPROVED CLEANOUT PLUGS LISTED FOR SCREW. SECURE GAS PIPING IN WALL AT DRYER. CAP ABANDON GAS TO WH. CONNECT OVENS, STOVE. SAFETY CABLE BRASS NIPPLES REQ AT MOP SINK FAUCET. REVISION FOR CHANGES OF WH. ELECTRICAL DISCON. INSTALL HAMMER ARRESTORS. PIPE WH DRAIN PAN. SUPPORT OVERHEAD ABS. TRIM OUT CLEANOUTS. SECURE SINKS. PROTECT ANY EXPOSED PLASTIC. INSP STOPPED.
09/10/2013 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
09/10/2013 PLUMBING - FINAL Partial Approval NEED STOVES TO BE WROKING FOR TEST