Permit: T13CM04016

Parcel: 12502021A


Addresses:

2910 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T13CM04016

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2013 FRAMING Approved IVRS - Inspection :*
07/19/2013 FRAMING Not ready for Inspection 1. 1/2" lag bolts required for 2"X2" stl. post.
07/17/2013 FRAMING Not ready for Inspection 1. A-1 detail one. Bottom track anchor metal studs to floor at 34" on center with one and a half inch power driven fasteners. Show that the correct fastener was used. A-1 detail two. 2"X2" steel post at 48" on center. half inch lag bolts required. Bolts installed are not tight. A-1 A shows partition extending one inch past the existing floor sink. Plumbers tape is not an approved strap. Support copper stub outs.
07/12/2013 FRAMING Not ready for Inspection 1. Partition not constructed per plan. See sheet A-1 Details #01 and #02. Isolate copper from the metal studs. Support copper in the walls. Support copper stub outs.