Inspection History Details
Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
Permit Number - T13CM03995
Inspection Description - BUILDING - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2013 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
09/25/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
09/20/2013 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/20/2013 | BUILDING - FINAL | Not ready for Inspection | 1. DUCT SMOKE DETECTORS REQUIRE AUDIO & VISUAL ALARMS 2. PROVIDE TEMP MIXING VALVES AT LAVS PER A.D.A. REQUIREMENTS 3. PROVIDE REVISED DETECTOR TEST 4. PROVIDE STERILIZATION REPORT 5. SINK TOO HIGH FOR A.D.A. COMPLIANCE 6. REMOVE SUPPLY AIR TO RESTROOMS 7. PROVIDE COMPLETE BALANCE REPORT |