Permit: T13CM03923

Parcel: 122163080


Addresses:

3858 E EDISON PL

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
09/11/2013 EXCAVATION/LAYOUT REBAR & ZON Approved
09/10/2013 EXCAVATION/LAYOUT REBAR & ZON Denied REBAR REQUIRES MIN 3" CLEAR FROM GROUND
09/06/2013 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection 1. Existing conditions do not meet the requirements of detail one on sheet S1.0 Is the overexcavation outside the slab to pour in place a footing? Where is the moisture barrier?