Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2013 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/05/2013 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/05/2013 | PLUMBING - FINAL | Denied | T & P DRAIN LINE CANNOT HAVE FLEX COPPER & MUST BE MIN 3/4" SMOOTH INTERIOR LEFT GAS CARD |
|
| 07/02/2013 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/02/2013 | PLUMBING - FINAL | Denied | 11 PSI TEST IS OK T & P DRAIN LINE NOT TO CODE. T & P MUST DRAIN DOWNHILL TO DAYLIGHT. PROVIDE MIN 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR ON WATER HEATER. PROVIDE A PERMIT FOR NEW WATER HEATER. REMOVE PIPE INSULATION FROM AROUND VENT CONNECTOR. |