Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T13CM03775
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
09/19/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/19/2013 | BUILDING - FINAL | Denied | 1. A/C DISCONNECT 3/4 K.O SEAL MISSING 2. A/C COMBINER RED WIRE LINE SIDE LOOSE & ANCHOR BOLT ON TOP 3. BOTH BOTTOM SCREWS ON INVERTERS LOOSE 4. ON ROOF PANEL WIRES, MORE THAN 18" SHOWING TO DIRECT SUN LIGHT |