Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/15/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/11/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/11/2013 | ELECTRIC - FINAL | Denied | 1. 2 GROUND RODS REQUIRED 6' MIN APART 2. BOND WATER & GAS PIPING 3. USE APPROVED 3R - J-BOX TO RE-CONNECT WIRING - EXISTING HAS TOO MANY HOLES IN IT |
|
| 07/09/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/27/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/27/2013 | ELECTRIC - FINAL | Denied | -RISER & FEEDER TOT MAIN BRKR HAS DAMAGE FROM OVERHEATING AND ALSO IS TOO SMALL FOR 60 AMP SERVICE - WIRE SIZE SHOULD BE #6 COPPER OR LARGER. SERVICE IS ENERGIZED AT THIS TIME - USE QUALIFIED OR LICENSED ELECTRICAL TO DO WORK |