Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T13CM03745
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
11/25/2013 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
11/25/2013 | BUILDING - FINAL | Partial Approval | ITEMS 4, 6, & 8 DATED 11/18/13 STILL NOT CORRECTED. AIR HANDLER HEAT STRIP NOT IDENTIFIED. | |
11/18/2013 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/18/2013 | BUILDING - FINAL | Not ready for Inspection | 1. RESTROOM EXHAUST CAN NOT BE ON SWITCH, INSTALL PER PLANS 2. PROVIDE "E" LIGHTING AT RESTROOM 3. PROVIDE "E" LIGHTING AT MEZZ, PERPLANS 4. WAREHOUSE LIGHTING NOT PER PLAN 5. PROVIDE SECONDARY DRAIN AT AIR HANDLER (LOWER) 6. AIR HANDLER (UPPER) O.S.A. DUCTING NOT INSTALLED 7. PROVIDE STERILIZATION REPORT 8. PROVIDE AIR BALANCE MINIMUM REQ 1. O.S.A. 2. RESTROOM EXHAUST 3. RESTROOM SUPPLY |