Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - RECONNECT
Permit Number - T13CM03681
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2013 | ELECTRIC - RECONNECT | Partial Approval | recon ok remove west porch or obtain a permit and rebuild it before this permit will be finalled out |
|
07/11/2013 | ELECTRIC - RECONNECT | Denied | call me - dan quinn -regarding how power was obtained to the front house, and what the plan is for the porch on the rear house | |
06/19/2013 | ELECTRIC - RECONNECT | Denied | UNIT 1 1) Install smokies in hall and sw bedroom 2) correct overfused #14 wire in panel 3) Properly terminate wires under panel gfi outlet UNIT 2 4) Install smokie outside bedroom NOTE: Although not in conjunction with the reconnect, you must obtain a permit and inspections for the unit 2 west porch, or remove it. |