Permit: T13CM03658

Parcel: 13324010C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T13CM03658

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/24/2013 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
11/14/2013 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/14/2013 PLUMBING - INTERMEDIATE Partial Approval PROVIDE PLENUM RATED WIRE INSIDE RETURN AIR PLENUM. PROVIDE A TRAP ON CONDENSATE DRAIN & A SECONDARY OVERFLOW SENSOR. OK TO INSULATE HOT WATER PIPING PER PLAN. PROVIDE MAIL PLATES AT WATER LINES FOR HVAC. PROVIDE BACKING AT SIDEWALK REGISTER BOXES. ISOLATE COPPER CONDENSATE DRAIN FROM KNOCKOUT IN PLENUM & RESTING ON METAL FRAMING.
09/12/2013 PLUMBING - INTERMEDIATE Partial Approval drain abs ok
need water supply