Permit: T13CM03657

Parcel: 133231460

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T13CM03657

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2014 FIRE - FINAL Approved All reports are in
05/19/2014 FIRE - FINAL Partial Approval Need annual fire sprinkler, fire alarm and 5 year check valve inspections done. After reports are in this permit will be closed out.
12/18/2013 FIRE - FINAL Denied Phase 2 of 3 approved
According to spec sheet for the sprinkler heads need to extend through ceiling tiles by max of 7/8 of an inch to min of 5/8 of an inch
09/07/2013 FIRE - FINAL Partial Approval 1. ok to occupy bldg 940 phase g.
08/26/2013 FIRE - FINAL Denied 1. Under permit number T12CM06369 the following was stated:
"IFC 907.2.2 combined Group B load for all floors is 500 or more or occupant load is more than 100 persons above or below the lowest level of exit discharge. You can use the first floor only at this time, but when going for the C of O final for the 2nd floor a completely fully operational fire alarm system that meets the IFC 907 and the NFPA 72 standards will be needed. "
2. Need to have sprinkler contractor to call in all of there permits before your final will be approved.