Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T13CM03657

Parcel: 133231460

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T13CM03657

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/07/2013 FIRE - ALARM FINAL Approved
08/26/2013 FIRE - ALARM FINAL Denied As stated on permit number T12CM06369 the following notice was given:
"IFC 907.2.2 combined Group B load for all floors is 500 or more or occupant load is more than 100 persons above or below the lowest level of exit discharge. You can use the first floor only at this time, but when going for the C of O final for the 2nd floor a completely fully operational fire alarm system that meets the IFC 907 and the NFPA 72 standards will be needed."