Permit: T13CM03657

Parcel: 133231460

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T13CM03657

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2013 FIRE SPKLR - FINAL Approved Phase 2 of 3 approved
According to spec sheet for the sprinkler heads need to extend through ceiling tiles by max of 7/8 of an inch to min of 5/8 of an inch
08/26/2013 FIRE SPKLR - FINAL Denied 1. There are some sprinkler heads even with the drop ceiling tiles sprinkler heads need to a min of 1 inch below drop ceiling at all times. Need to walk floor and lower all heads that are not 1 inch below.