Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2014 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 10/31/2014 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/31/2014 | PLUMBING - FINAL | Partial Approval | 1. INSTALL METAL LINE AT HOSE BIBB FOR PROTECTION 2. INSTALL ANTI-SIPHON VALVE AT HOSE BIBB |
|
| 07/17/2014 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/17/2014 | PLUMBING - FINAL | Not ready for Inspection | 30 UNITS OR SO 75 INCH IS NOT LARGE ENOUGH. PROVIDE FIXTURE UNIT DEMAND, TOTAL DEVELOPED LENGTH AND WATER PRESSURE ON A PLAN AND GET CITY PLAN REVIEW NOTE: MIN 12" COVER, TRACOR WIRE REQUIRED | |
| 07/19/2013 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/19/2013 | PLUMBING - FINAL | Not ready for Inspection | MULTIPLE UNITS & LAUNDRY; PLEASE PROVIDE A PLAN FOR SIZING BACKFLOW PROTECTION FOR ALL HOSE BIBS. ACCESS TO VALVEST, ETC...EXPOSE FOR INSP |