Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/01/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/01/2013 | ELECTRIC - FINAL | Denied | 1. J. BOX TO BE BOND BY #10 NOT 12 2. NEUTRAL TO STOVE TO DRYER IN J. BOX TO SERVICE PANEL TOO SMALL 3. NEUTRAL FROM STOVE TO DRYER & J. BOX TO BE TAPED NOT BARE 4. CHASE NIPPLE ON J. BOX TO LB MISSING LOCK NUT |