Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T13CM03620
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
12/03/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
12/03/2013 | MECHANICAL - FINAL | Denied | MECH CONTRACTOR TO BE ON SITE AT NEXT INSPECTION | |
09/24/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/24/2013 | MECHANICAL - FINAL | Denied | MARK THE LOWER SECTION OF DATA PLATE FOR PROPER HEAT STRIP & FUSE ACCORDINGLY AS PER 230 V DATA. 45 AMP WON'T WORK WITH ANY OF THE STRIPS. UNIT IS DOUBLE TRAPPED. REMOVE THE 2ND TRAP. SECURE THE ELEC DISCONNECT. SOME OF THE CANVAS CONNECTOR IS STILL EXPOSED TO SUNLIGHT. COVER ALL PORTIONS. | |
07/18/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/15/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/15/2013 | MECHANICAL - FINAL | Denied | PROVIDE ACCESS TO ROOF |