Permit: T13CM03620

Parcel: 133403480


Addresses:

7839 E ROSEWOOD ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T13CM03620

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/05/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/03/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/03/2013 MECHANICAL - FINAL Denied MECH CONTRACTOR TO BE ON SITE AT NEXT INSPECTION
09/24/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/24/2013 MECHANICAL - FINAL Denied MARK THE LOWER SECTION OF DATA PLATE FOR PROPER HEAT STRIP & FUSE ACCORDINGLY AS PER 230 V DATA. 45 AMP WON'T WORK WITH ANY OF THE STRIPS. UNIT IS DOUBLE TRAPPED. REMOVE THE 2ND TRAP. SECURE THE ELEC DISCONNECT. SOME OF THE CANVAS CONNECTOR IS STILL EXPOSED TO SUNLIGHT. COVER ALL PORTIONS.
07/18/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/15/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/15/2013 MECHANICAL - FINAL Denied PROVIDE ACCESS TO ROOF