Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/24/2013 |
PLUMBING - FINAL |
|
Approved |
|
| 07/19/2013 |
PLUMBING - FINAL |
|
Not ready for Inspection |
1. No message. No access. Door locked. |
| 07/18/2013 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 07/11/2013 |
PLUMBING - FINAL |
|
Not ready for Inspection |
1. Where gas appliances are not yet set, cap off the gas valve. See note from 07/03/13 |
| 07/03/2013 |
PLUMBING - FINAL |
|
Not ready for Inspection |
1. At the water heater- TandP relief drain may not have a threaded end. Require accessible shut off at cold inlet to water heater. Continued not ready may result in a reinspection fee. |
| 06/27/2013 |
PLUMBING - FINAL |
|
Not ready for Inspection |
1. In the future- use a gauge in 1/10 pound incrementation. Where gas appliances are not yet set, cap off gas valve. At water heater- T and P elief drain may not have a threaded end. Require accessible shut off valve at cold inlet. |