Permit: T13CM03582

Parcel: 113030820


Addresses:

3650 N 1ST AV #100

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
04/08/2014 FIRE - FINAL Approved
03/28/2014 FIRE - FINAL Partial Approval
03/24/2014 FIRE - FINAL Denied 1. Need separate plan and permit for the installation of the fire alarm system as stamped on the cover page for the racks.
2. Need separate plan and permit for the install of the fire alarm system.
3. Post suite number above main door
4. Remove drop bar locks and padlocks on all egress doors only use approved locking devices. IFC 1008.1.9.3
5. According to the plans on PG A1.O under the section of the new "floor plan keynotes" #5 states "Existing door and hardware to remain, blank hardware at exterior" two doors were covered over with 5/8" board rendering the doors non-functional and #6 states existing store front door to be removed and in filled with new storefront window system to match adjacent type and style" door hardware was remove but not the doors and they do not match storefront. You will need to have the plans corrected as to what is on site and have revise plans approved.
6. Back up lighting is required under IFC 1006.2 - in aisles - stairs - egress doors - corridors.
7. Key box is required under IFC 506.1
8. Egress doors rendered non-functional shall be label on the outside middle of door(s) "THIS DOOR BLOCKED" ¾" wide 6" high lettering. IFC 504.2