Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2013 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 06/14/2013 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/14/2013 | PLUMBING - GAS PRESSURE TEST | Denied | INSTALL CARBON MONOXIDE DETECTORS OUTSIDE OF BEDROOMS. SECURE WH VENTS W/ SCREWS. NEW WH REQUIRES A CORRECTION FOR RELIEF VALVE DRAIN - DRAIN MAY NOT BE TRAPPED. PROIVDE NEW GAS VALVES. SEDIMENT TRAP REQUIRES. PIIPING MAY NOT REDUCE IN SIZE PRIOR TO BRANCH CONNECTION. INSTALL PER PLAN. PROVIDE A FULL-SIZED TOE. TEST W/ A 15 PSI GAUGE. FILE OFF BURRS ON UNISTRUT |