Permit: T13CM03442

Parcel: 12709007J

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
10/03/2013 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
10/02/2013 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/02/2013 MECHANICAL - ABOVE CEILING Partial Approval FLEX DUCT MANUFACTURER REQUIRES BEADED CONNECTIONS. SMACNA REQUIRES MIN 2" TALL COLLARS ON DIFFUSERS. SECURE DIFFUSERS TO STRUCTURE OR TO MAIN RUNNER OF T BAR.