Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2013 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 10/02/2013 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* |
| 10/02/2013 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
FLEX DUCT MANUFACTURER REQUIRES BEADED CONNECTIONS. SMACNA REQUIRES MIN 2" TALL COLLARS ON DIFFUSERS. SECURE DIFFUSERS TO STRUCTURE OR TO MAIN RUNNER OF T BAR. |