Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2013 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* | |
| 09/26/2013 | PLUMBING - GAS PRESSURE TEST | Approved | - UNITS 1, 2, 4, & 5 APPROVED - UNIT 3 DENIED GASLINE LEAKING - UNIT 7: 1. REINFORCE STUDS 2. SEPARATION OF HEAT SOURCE FOR FURNACE 3. PROTECT ABS PIPE IN KITCHEN (METAL CLIPS) 4. PROTECTION OF ELEC WIRING ( 1 1/4") 5. REINFORCE WATER LINE (WATER HEATER) 6. PANEL FEEDERS SHOULD BE PER PLAN 7. MISSING CO DETECTORS 8. UNIT 3 GAS PRESSURE FAILED 9. UNIT 4 PROTECT EXPOSED WIRING 10. VACUUM BREAKER ON SPICKET |
|
| 09/17/2013 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* |