Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/11/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/11/2013 | ELECTRIC - FINAL | Denied | EQUIP NOT SUITABLE AS SERVICE EQUIP UNTIL NEUTRAL & GROUND BONDED BY CUSTOMER, AS PER LISTING & WIRING DIAGRAM INSTRUCTIONS, INSIDE DOOR NEC - 110-3, 250.24 THRU 250.28. **A RE-INSPECTION FEE WILL BE ASSESSED NEXT INSPECTION IF NO COMPLIANCE** |
|
| 10/10/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 10/10/2013 | ELECTRIC - FINAL | Denied | BOND NEUTRAL IN SERVICE CABINET |