Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/28/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/28/2013 | MECHANICAL - FINAL | Denied | 1. CONDENSATE EXPOSED TO DAYLIGHT NOT PROTECTED 2. UNIT DATA PLATE NOT IDENTIFIED. THIS PERMIT IS BEING RE-FEED DUE TO WORK NOT BEING COMPLETED |
|
| 06/12/2013 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/12/2013 | MECHANICAL - FINAL | Not ready for Inspection | 1. CONDENSATE NOT PROPERLY TERMINTATED 2. ALL PVC MUST HAVE PRIMERED JOINTS, PRIMER IS TO BE APPLIED PRIOR TO GLUE 3.PVC EXPOSED TO DAYLIGHT MUST BE COATED FOR UV PROTECTION 4. UNIT DATA PLATE NOT IDENTIFIED 5. WIRING NOT TO CODE, NOT PROPERLY COLOR CODED |