Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T13CM03370

Parcel: 10602197B


Addresses:

3730 N STONE AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/05/2013 PLUMBING - GAS PRESSURE TEST Approved
08/30/2013 PLUMBING - GAS PRESSURE TEST Not ready for Inspection 1. Please use correct gauge. sixty pound test to be a hundred pound gauge in one pound incrementation. Unable to verify listing on the pipe. To be A53, or A53A on each section of pipe.