Permit: T13CM03366

Parcel: 13324009A

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/20/2013 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
09/20/2013 MECHANICAL - FINAL Partial Approval PROVIDE A BUSHING AT CONNECTION TO 100 AMP DISCONNECT. PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS. MAX 20 TONS ALLOWED ON 1" CONDENSATE DRAIN. PROVIDE A DATA PLATE FOR 20 TON AIR HANDLER. PROVIDE FRESH AIR INTAKES. PROVIDE AIR BALANCE REPORT.