Permit: T13CM03334

Parcel: 121031010


Addresses:

5743 E LINDEN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/02/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/11/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/11/2013 MECHANICAL - FINAL Denied ONE LOOSE STRAND - CORRECT
LEAK ON CONDENSATE
BOND BUSHING REQ AT CONDUIT CONNECTION TO DISCONNECT BOX
06/19/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/19/2013 MECHANICAL - FINAL Denied HEAT STRIP STILL NOT FUSED CORRECTLY. MARK UNIT DATA PLATE W/ PROPER HEAT STRIP INSTALLED. STILL LOOSE WIRE STRANDS IN DISCONNECT
06/11/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/11/2013 MECHANICAL - FINAL Denied SECURE THE ELEC DISCONNECT. SECURE THE ANGLE IRON STAND TO STRUCTURE. TIGHTEN LOOSE ELEC CONNECTION AT UNIT. HEAT STRIP NOT FUSED CORRECTLY. MARK UNIT DATA PLATE. REPAIR LOOSE WIRE STRAND AT LOAD CONNECTION IN DISCONNECT. PAINT EXPOSED PVC W/ LATEX PAINT. PROPERLY SUPPORT DRAIN LINE.