Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/11/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/11/2013 | MECHANICAL - FINAL | Denied | ONE LOOSE STRAND - CORRECT LEAK ON CONDENSATE BOND BUSHING REQ AT CONDUIT CONNECTION TO DISCONNECT BOX |
|
| 06/19/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/19/2013 | MECHANICAL - FINAL | Denied | HEAT STRIP STILL NOT FUSED CORRECTLY. MARK UNIT DATA PLATE W/ PROPER HEAT STRIP INSTALLED. STILL LOOSE WIRE STRANDS IN DISCONNECT | |
| 06/11/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/11/2013 | MECHANICAL - FINAL | Denied | SECURE THE ELEC DISCONNECT. SECURE THE ANGLE IRON STAND TO STRUCTURE. TIGHTEN LOOSE ELEC CONNECTION AT UNIT. HEAT STRIP NOT FUSED CORRECTLY. MARK UNIT DATA PLATE. REPAIR LOOSE WIRE STRAND AT LOAD CONNECTION IN DISCONNECT. PAINT EXPOSED PVC W/ LATEX PAINT. PROPERLY SUPPORT DRAIN LINE. |