Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/08/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/08/2013 | MECHANICAL - FINAL | Partial Approval | 1. PROVIDE MINIMUM 6"CLEARANCE TO COMBUSTIBLES (EASY TRAP) FROM SINGLE WALL FLUE CONDUTOR 2. CONDENSATE NOT PROPERLY TERMINATED 3. REMOVE TAPE FROM LINE SET INSULATION AND COAT WITH AN APPROVED UV COATING 4. PROVIDE K.O. PLUG AT DISCONNECT |