Permit: T13CM03313

Parcel: 126091000


Addresses:

4241 E BURNS ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/28/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/18/2013 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
10/18/2013 MECHANICAL - FINAL Partial Approval 1/2" GAS PIPE NOT ADEQUATE FOR 135,000 BTU FURNACE. 3/4" IF WITHIN 60' FROM METER OR 1" IF WITHIN 175' FROM METER. PROVIDE A PRESSURE TEST IF INSTALLING A NEW GAS LINE.