Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2013 | FIRE - FINAL | Approved | ||
| 08/19/2013 | FIRE - FINAL | Denied | 1. Need annual sprinkler inspection completed 2. Replace painted recesses escutcheon caps on sprinkler in the dining area. 3. Correct sprinkler coverage in freezer room/storage room sprinkler is over 8 feet off wall. 4. Have kitchen and floor areas clear of storage bad housekeeping. 5. Have set of approved stamped plans on site for finals. 6. Remove all wiring from sprinlker piping. |
|
| 08/16/2013 | FIRE - FINAL | Denied | 1. called the number on permit its mike he did not know anything about this i showed up know one was there. |