Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/05/2013 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 06/04/2013 |
PLUMBING - FINAL |
|
Partial Approval |
14 PSI TEST IS OK. LEFT GAS CARD. T & P DRAIN CANNOT TERMINATE INTO CONDENSATE DRAIN. PROVIDE MIN 3 SCREWS IN EACH JOINT OF VENT CONNECTOR. USE HIGH TEMP CAULK ON VENTING IF NEEDED. DO NOT USE COLD WATER PVC ON T & P DRAIN. |
| 06/03/2013 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection :* |