Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T13CM03271
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/07/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/07/2013 | MECHANICAL - FINAL | Denied | SUPPORT DRAIN PIPING AND LINE SET. REINSTALL ALL PVC JOINTS USING PURPLE PRIMER IS REQUIRED BY CODE. RECONNECT DRYER VENT. SEAL WALL PENETRATION, TURN DRAIN DOWN. CONDENSER IS REQUIRED TO BE 3 1/2" ABOVE GRADE. | |
| 06/03/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/31/2013 | MECHANICAL - FINAL | Denied | - OVERFLOW SESNSOR NEEDED OR SECONDARY LINE FOR CONDENSATE LINE - DISASTER PAN NEEDED TO EXTEND OUTSIDE FAN UNIT |