Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM03188
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2013 | FIRE - FINAL | Approved | ||
09/05/2013 | FIRE - FINAL | Denied | 1. Label keys for key box - fire panel - front door 2. Address number posted per handout given 15" 3. Need a sign on the lid cover for the inspector test valve in the dressing room southeast corner. |
|
09/04/2013 | FIRE - FINAL | Denied | 1. Need phone lines 2. Label keys for key box - fire panel - front door 3. Address number posted per handout given 15" 4. Need the UL/FM list for the monitoring company 5. Testing was completed on fire alarm system all passed but will need to do a test on water flow and tamper for the phone lines. 6. Upright coverage needs correction on sales floor heads cannot be more than 12 inches from deck measuring from the insulation 7. Upright coverage needs correction in storage room southwest corner heads cannot be more than 12 inches from deck. 8. Correct upright coverage southwest corner head to far off wall 11 feet. 9. Southwest dressing rooms install upright coverage that was removed for the drop ceiling coverage. 10. In office area (northeast) upright coverage blocked by main beam need to correct for proper coverage. 11. Need a sign on the lid cover for the inspector test valve in the dressing room southeast corner. |