Permit: T13CM03188

Parcel: 119180870


Addresses:

3660 S 16TH AV

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
09/11/2013 FIRE - ALARM FINAL Approved
09/09/2013 FIRE - ALARM FINAL Denied Need to have water flow signal go to monitoring company as a water flow and no as zone number.
09/05/2013 FIRE - ALARM FINAL Partial Approval 1. Need to separate water flow signal out to report to monitoring company as a water flow.
2. Install lock outs on breakers to the FACP - Sprinkler bell - Monitoring system.
I tested all duct detectors to the A/C units, all units shut completely down and reported to the FACP system.
09/04/2013 FIRE - ALARM FINAL Denied NO PHONE LINES
1. Testing was completed on fire alarm system all passed but will need to do a test on water flow and tamper for the phone lines.
2. Need lock out on breaker