Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T13CM03188

Parcel: 119180870


Addresses:

3660 S 16TH AV


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T13CM03188

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2013 FIRE SPKLR - FINAL Approved
09/09/2013 FIRE SPKLR - FINAL Approved
09/05/2013 FIRE SPKLR - FINAL Denied Need a sign on the lid cover for the inspector test valve in the dressing room southeast corner.
09/04/2013 FIRE SPKLR - FINAL Denied 1. Upright coverage needs correction on sales floor heads cannot be more than 12 inches from deck measuring from the insulation
2. Upright coverage needs correction in storage room southwest corner heads cannot be more than 12 inches from deck.
3. Correct upright coverage southwest corner head to far off wall 11 feet.
4. Southwest dressing rooms install upright coverage that was removed for the drop ceiling coverage.
5. In office area (northeast) upright coverage blocked by main beam need to correct for proper coverage.
6. Need a sign on the lid cover for the inspector test valve in the dressing room southeast corner.