Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13CM03188
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2013 | FIRE SPKLR - FINAL | Approved | ||
09/09/2013 | FIRE SPKLR - FINAL | Approved | ||
09/05/2013 | FIRE SPKLR - FINAL | Denied | Need a sign on the lid cover for the inspector test valve in the dressing room southeast corner. | |
09/04/2013 | FIRE SPKLR - FINAL | Denied | 1. Upright coverage needs correction on sales floor heads cannot be more than 12 inches from deck measuring from the insulation 2. Upright coverage needs correction in storage room southwest corner heads cannot be more than 12 inches from deck. 3. Correct upright coverage southwest corner head to far off wall 11 feet. 4. Southwest dressing rooms install upright coverage that was removed for the drop ceiling coverage. 5. In office area (northeast) upright coverage blocked by main beam need to correct for proper coverage. 6. Need a sign on the lid cover for the inspector test valve in the dressing room southeast corner. |