06/25/2015 | FIRE - FINAL | Approved | ||
06/24/2015 | FIRE - FINAL | Partial Approval | 1. Okay for TCO. 2. Disabling Delayed egress doors till repairs are done. 3. Current hardware is normal operating Panic Hardware. |
|
06/19/2015 | FIRE - FINAL | Partial Approval | 1. Okay to stock. 2. Need delayed egress locks tied into Fire Alarm. |
|
06/16/2015 | FIRE - FINAL | Denied | 1. ITV test valve bad will not shut down water leaks by 2. WMG failed repair or replace 3. Straighten out the FDC make it level 4. Need to get monitoring system up and running 5. Need to test EM lighting and exit signs by shutting down the power |
|
06/01/2015 | FIRE - FINAL | Not ready for Inspection | 1. Need subcontractors to call in their permits i.e. fire alarm and fire sprinkler 2. Correct sprinkler upright coverage by riser in process area spray pattern blocked by duct work 3. Need to remove the ceiling tiles to check the upright coverage on sales floor where the air handlers (A/C units X7) are installed to make sure the upright spray pattern is not blocked. 4. Please label all breakers for exit signs and back up lighting for testing with the following "EM LTS." 5. Fire extinguishers shall be posted 75' foot travel distance 1 for every 1500 sq. ft. of building size and signs posted for ez identification of location. 6. Need key box installed by front door need the following keys in box; for the front main entrance door, FACP, pull stations and riser if using chain and pad lock, please I.D. each key with a metal key tag telling you what it is used for. 7. Need to post address numbers on front of building 15 inch size - handout given. |